Bacharach QV2 Manuel d'utilisateur Page 1

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Pompes à eau Bacharach QV2. refrigeration BY DAVE DEMMA Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 8
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
that the oil failure switch was the culprit.
After relieving the liquid refrigerant
from the crankcase you checked the oil
level. It was a little on the low side at 1/4
of a glass, but within the manufacturers
recommended limits. You carefully
restarted the compressor and proceeded
to check the net oil pressure. It was
measured to be 26 psi; again well within
the manufacturers specification.
Being a thorough technician, you
went the extra mile and verified the cor-
rect operation of the oil failure control.
You found the controls switch opened
45 seconds after the net oil pressure had
fallen below 6.5 psi; perfectly within the
specification for the make/model of the
compressor. No visible cause was identi-
fied. This is a nuisance oil failure trip.
How inconvenient.
Let’s be clear though. The only nui-
sance regarding this scenario is that a
reason for the oil failure trip cannot be
easily determined. To imply that an oil
failure trip happens intermittently for no
reason implies that oil failure controls
have a mind of their own, and periodi-
cally decide to shut off a compressor
simply to add spice to the technicians
life. Nothing could be further from the
truth. Unless an oil failure control is
defective, the only time it will trip is
when the compressors net oil pressure
falls below the controls cut-in point for
the specified amount of time necessary
for the control to lockout.
REAL OIL PRESSURE
Understanding component operation
always makes troubleshooting system
problems easier; but first a brief explana-
tion of the term “net oil pressure” is
required. The oil pump inlet is fed
through a screen located in the compres-
sor sump, so crankcase pressure would be
the same as oil pump inlet pressure. The
pump takes this oil at crankcase pressure
and increases its pressure to some value
above crankcase pressure. Unless the
crankcase pressure is 0 psi, the oil pump
outlet pressure does not tell the complete
story. The real oil pressure, or “net oil
pressure,” is the difference between
pump inlet pressure (crankcase pressure)
and pump outlet pressure (discharge
pressure).
A brief review of how oil failure con-
trols operate is in order. Unlike the typi-
cal low, high, or dual pressure control,
which has a single switch
in it, the oil failure control
requires two separate cir-
cuits to cause a lockout
after experiencing low net
oil pressure for a pre-
determined time (see
Figure 1).
The control circuit
switch
SC1 is a time delay switch
which is wired in series (at
terminals L and M) with
the other required controls
in the holding coil circuit
for the compressor motor
starter. It is considered the
slave in this arrangement,
and only opens when acted
upon by the time delay heater circuit. In
most applications SC1 would be a manu-
al reset switch. However; if a start-stop sta-
tion were used, an oil failure control with
an automatic reset switch could be used.
With this configuration an oil failure
control trip would cause the start-stop
THE GOODS ON OIL FAILURE TRIPS
refrigeration
BY DAVE DEMMA
Do you remember that service call you were dispatched to where the frozen food was melting
in the display cases? Upon arrival you found the compressor off; apparently for quite some
time as its body was stone cold. A quick check of the control circuit with a voltmeter revealed
station to open, locking out the compres-
sor starter’s holding coil circuit. While
this provides foolproof lockout from low
oil pressure, oil failures with this control
arrangement are more difficult to trou-
bleshoot. An automatic reset oil failure
control that trips the start-stop station
when low oil pressure occurs does not
leave any evidence that low oil pressure
was the problem for compressor lock-out.
The time delay heater circuit
This circuit requires a 208/240 volt sup-
ply to be applied between terminals V1
and 2 (or 120V between terminals V and
2). P1 is a normally closed differential
pressure switch which is connected to the
compressor crankcase and the oil pump
discharge. It measures net oil pressure.
P1 opens when the net oil pressure is
above the cut-in point for the control,
however the cut-in point will vary
depending on the compressor manufac-
turers specification. Some controls allow
for adjustment to the cut-in point, and
others are preset. H is a resistance heater;
the device which trips switch SC1 when
CONTINUED ON PAGE 90
86 HPAC 80 years MARCH 2006
FIGURE 1
OIL FAILURE CONTROL
HPAC02_086,090,092 3/1/06 10:45 AM Page 86
Vue de la page 0
1 2 3 4 5 6 7 8

Résumé du contenu

Page 1 - 80 years MARCH 2006

that the oil failure switch was the culprit.After relieving the liquid refrigerantfrom the crankcase you checked the oillevel. It was a little on the

Page 2 - SHOW & TELL BACHARACH

MARCH 2006 80 years •HPAC 87SHOW & TELL BACHARACHPRESENTED BY•Refrigerant Vacuum Pumps• Two stage rotary vane pump• 1/4” and 3/8” flare and 1/2

Page 3 - Refrigerants

HONEYWELL GENETRON‚ REFRIGERANTS:THE BEST OPTIONS FOR R-22 REPLACEMENTAs R-22 becomes less available due to allocation reductions by Environment Canad

Page 4 - Circle #47

St. Lawrence Chemical Inc.Exclusive distributor of Genetron refrigerants in CanadaOntario and Western Canada, Tel: 416-243-9615 Fax: 416-243-9731Queb

Page 5 - Cooling Systems Inc

refrigeration CONTINUED FROM PAGE 86powered for pre-determined amount oftime. DR is a simple resistor whichallows this circuit to be powered byeither

Page 6 - A Refreshing Change

SHOW & TELL ARKEMAPRESENTED BY•Arkema's Forane®410A and 407C are the contractors best choice for R-22 replacement and retro-fit. Meet the

Page 7 - RATE THE ARTICLE!

refrigeration CONTINUED FROM PAGE 90RATE THE ARTICLE!Will this information be useful? Please circle the appropriate numberon the Reader Postcard. Tha

Page 8 - CUSTOM HEAT TRANSFER COILS

MARCH 2006 80 years •HPAC 93SHOW & TELL MADOKCUSTOM HEAT TRANSFER COILSNew and Replacement Coils - Copper Tube / Aluminum Plate FinMADOK’s earl

Commentaires sur ces manuels

Pas de commentaire